■CONTACTOR DATA
Model |
ZLJM-400C/□A3 |
Contact form |
Bi-stable |
Contact Rating (at Resistive Load) |
400A×60VDC (DC-1) |
Contact Voltage Drop |
Max.80mV @400A |
Insulation Resistance |
Min. 100MΩ at 500VDC |
Dielectric Strength (Between Insulated Electric Parts) |
1000VAC 50 Hz/60 Hz (1 minute) |
Pick-up time |
Max. 30mSec. |
Drop-out time |
Max. 30mSec. |
Max. bounce time of main contact |
3mS |
Impulse Width |
0.5S~1S |
Mounting Way |
Arbitrarily |
Working Duty |
Continuous |
■COIL DATA
Model |
Coil Voltage(V) |
Coil Working voltage(V) |
Pick-up Voltage(V) |
Drop-out Voltage(V) |
Starting Current (A) |
Coil power dissipation(W) |
ZLJM-400C/A3 |
12 |
0.8US~1.2US |
20%~80% |
20%~80% |
≤3.2 |
40 |
24 |
≤1.6 |
|||||
48 |
≤0.8 |
|||||
60 |
≤0.64 |
■Part Numbering System
Example: ZLJM-400C/48.S; said: Magnetic latching DC Contactor, 400A for DC-1 load rated current, coil voltage 48V DC, with aux. contact.
■SHAPE INSTALLATION AND CIRCUIT DIAGRAM
1、ZLJM-400C/□ A3 unit (mm)
2、ZLJM-400C/□.S A3
Dimension(mm) |
Tolerance grade not noted(mm) |
0~30 |
±0.3 |
30~60 |
±0.5 |
60~100 |
±1 |
>100 |
±2 |
NOTE:
1. Product coil is excited by positive and negative pluse,500mS≤t≤1S.long time continuous energizing is not allowed. Operation frequency should be no more than 6 ops/min. It`s square pulse(“+” connect with positive pulse, “-” connect with negative pulse) and positive pulse makes the contact close while negative pulse makes the contact open after the excitation ,the permanent magnet in product keeps the state of the contact.