■Contactor Data
Main Part No. |
DYZ1-63C/B60.S |
Contact type |
Bi-stable |
Rated load current of contact (Resistive load) |
63A×80V DC |
Contact voltage drop |
≤40mV@63A |
Insulation resistance |
Min. 100MΩ at 500VDC |
Dielectric strength (Between Insulated Electric Parts) |
1500VAC 50 HZ/60 HZ (1 minute) Leak current<1mA |
Vibration |
(10~200)HZ、≤3.5g |
Shock |
(60~100)ops/minute、≤4g |
Lightning stroke |
8/20us 10/20KA lightning test ±5 times each |
Pollution level |
III |
Working duty |
Continuous |
■Coil Data
P/N |
Coil voltage |
Coil operating voltage(V) |
Pick-up voltage(V) |
Drop-out voltage(V) |
Start power(A) |
Coil Power(W) |
DYZ1-63C |
60V |
36~72 |
≤42 |
≤42 |
≤0.4 |
≤24 |
48V |
28.8~57.6 |
≤33.6 |
≤33.6 |
≤0.5 |
||
24V |
14.4~28.8 |
≤16.8 |
≤16.8 |
≤1 |
||
12V |
7.2~14.4 |
≤8.4 |
≤8.4 |
≤2 |
■Part Numbering System
Example: DYZ1-63 - c/B60. S. indicates Magnetic latching DC contactor, rated current at DC-1 load is 63A, coil voltage is DC60V.Products with magnetic blowing, with auxiliary contact.
■Shape installation and circuit diagram (Unit: mm)
DYZ1-63C/□.S
Dimension(mm) |
Tolerance grade not noted(mm) |
0~30 |
±0.3 |
30~60 |
±0.5 |
60~100 |
±1 |
大于100 |
±2 |
Note:
1. Main circuit connects copper bus bar which is silver plated;
2. Auxiliary contact connecting plate is silver plated;
3. The product coil has positive and negative pulse excitation, excitation time 50ms≤ T ≤200s.The coil shall not be continuously energized for long periods, the operating frequency shall not exceed 6 times per minute, and the pulse shall be square wave. Positive pulse (" + "is connected to the power supply positive," - "is connected to the power supply negative) makes the contact pick-up, negative pulse (" +" is connected to the power supply negative, "-" is connected to the power supply positive) makes the contact drop-out. After the coil is de-excited, the state of the contactor is maintained in permanent magnetic.